Product Overview:
RBK-6000-ZL9 gas alarm controller external standby power supply (standby power optional), RBK-6000-ZL9N gas alarm controller built-in standby power supply (gas special). It can be matched with our company's RZL09 series gas detector to form an industrial gas alarm system.
The product design follows the national standard GB16808-2008, the system has beautiful appearance, clear display interface, simple operation, and the whole product design adopts modular structure design, which is easy to maintain.
The gas alarm controller obtains the gas detector information through inquiry, and displays the corresponding concentration and status of the detector through the LCD through high-speed CPU data processing, and outputs the corresponding controller signal.
Features:
2 groups of switching outputs.
● M-BUS two-bus power supply communication mode is non-polar.
● The CPU adopts 16-bit single-chip microcomputer, which runs fast and has high reliability.
● The instrument password operation can be used to zero and calibrate the detector.
● The instrument adopts multiple password protection, with different operation levels, different passwords and high security.
● High-brightness LCD display is adopted, which can display the working time, alarm and fault record of the host in real time. Automatic fault detection, which can accurately indicate the location and type of fault. Large-capacity alarm, on/off record, historical record without loss of power failure.
Product Parameters:
| Rated voltage |
Mains:AC 220V±15% |
| Maximum power |
20W |
| Signal input |
M-BUS two-bus, single-circuit |
| Relay capacity |
AC 250V/5A Or DC 30V/5A |
| Storage capacity |
Alarm records, 100 start-up records, and 100 Shutdown records |
| Operating temperature |
0℃~40℃ |
| Operating humidity |
≤95%RH(No condensation) |
| Pressure range |
86kPa~106kPa |
| Capacity |
≤ No. 9 |
| IP rating |
IP30 |
| Installation: |
Wall-mounted |
| Dimensions |
288mm*220mm*85mm |
| Communication distance |
≤800m(RVS 2*2.5mm 2) |
| Equipped with gas detectors |
GT-RZLED09、GT-RZLCD09、GTYQ-RZLED09、GTYQ-RZLCD09 |
| Enforce the standard |
GB 16808-2008 |